Tag Archives: RV Furnace Voltage

RV Furnace Maintenance

11 Wednesday Dec 2019

Posted by Coach-Net in RV Information, Tech Tips

≈ 4 Comments

Tags

RV Furnace, RV Furnace Voltage, RV winter maintenance, winter camping, winter rving, Winter Travel

RV Furnace Maintenance

Just because cold weather is right around the corner, or has already frozen the corner in your neck of the woods, doesn’t mean you’re done camping for the year!  More RVers are using their rigs for winter activities such as skiing, ice skating, and even ice fishing trips rather than trying to find a hotel miles away from the activities.  If you plan to do any cold weather camping, it’s important to make sure your RV furnace is operating properly and some tips to make it run more efficiently.

Inside Motor Home

Let’s first cover how the liquid propane (LP) furnace operates;

The thermostat is set to the desired temperature, once the inside temperature drops below that setting, the thermostat calls for heat from the furnace.  Most thermostats have a variance that can be as much as 4 degrees below the setting.  Your RV thermostat is powered by the 12-volt house battery system, therefore you can not replace it with a residential model such as the NEST or other devices as they operate on 24-volt power.  Older models were designed with a bi-metal interior coil that would shrink and expand with temperature changes and we all remember the old “mercury in a tube” type models!  These should be changed with a newer RV specific model.  Also, make sure you match your heating and cooling system to the proper thermostat as some control both the heater and air conditioner, others have a heat pump, and some models have several zones with temperature sensors in individual rooms.

Once the thermostat calls for heat, the control module starts the blower motor inside the furnace which blows out any older air that may be trapped inside the burner assembly which could contain trace amounts of LP.  This is exhausted outside through the vent tube.  The blower motor also draws cold air from inside the RV and routes it back over the burner tubes and through the interior vents.  This forced air pushed up a “sail switch” located behind the burner tubes and once the switch reaches the desired height, creates a closed circuit that tells the module board there is sufficient airflow and to open the gas valve and light the burner assembly.  One common problem with RV heaters is low house batteries that will not provide enough airflow to raise the switch!  If your batteries are below 11-volts, the blower fan will run, but the unit will not light.  This can also be deceiving when the furnace does light and runs for some time and then just the blower runs.  This typically means the house batteries started off with enough voltage, but then drained fast due to sulfation.

Also, if you have a few heat vents closed, a rug over the floor vents, or a pinched or kinked supply hose in the rig, it will restrict the airflow and the sail switch will not rise, therefore the gas valve will not open and the spark igniter will not light the flame.

Heat Exancher

Once the sail switch has verified sufficient airflow and created the closed circuit, the circuit board will open the gas valve which you should hear a distinctive click, followed by the spark ignitor clicking and lighting the LP mixture in the burner assembly.  Then the heat exchanger will heat to approximately 200 and the air wheel pushes fresh air over the heat exchanger to provide warm air to the inside of the rig.

(Sail Switch)

Sail Switch

The air going through the heat exchanger is exhausted to the outside of the RV through an exhaust vent.  Some models have two vents on the outside of the rig, with the upper vent designed for fresh air, and the lower for heated air coming out of the heat exchanger.

Heat Exchanger 2

 

Tips to make your heater run more efficiently

As mentioned before, do not cover vents with carpeting, rugs, or close off to many vents inside the rig.  Not only does it limit airflow at the sail switch, it will also build up excess heat in the heat chamber and trigger the high limit switch.

Floor Vent

(High Limit Switch)

Verify your exterior exhaust and intake vents are unobstructed and your house batteries are in good working order. Lead-acid batteries will become sulfated and lose storage capacity if not properly charged and maintained.  Verify your LP pressure is sufficient which should be at 11” of water column and should be checked by a certified technician.  Make sure your LP regulator is not exposed to the elements and does not get snow and ice buried around it.

High Limit Switch

Troubleshooting Tips:

No Operation

If the furnace does not light, verify there is 12-volts going to the thermostat and then at the control board on the furnace.

Propane

Check to see if the blower motor is working but the valve is not opening and trying to spark.  If the blower motor is not working, check to make sure there is no obstruction such as a mouse nest.  This requires removal of the shroud or often time the entire unit to access.  Removal will also allow you to test the sail switch and high-temperature switch which can be done with an ohm resistance test.

Blower runs, no heat

Test for 12-volt at the control module, listen for the gas valve to open with a click, listen for spark attempt.  If the gas valve does not open, it could be a faulty control board.  If it attempts to spark, it could be a cracked ceramic insulator on the lighter probe causing the spark to follow the crack to ground known as carbon tracking which means the spark does not get to the burner.  It could also mean a dirty or contaminated spark ignitor or improper gap. And finally, it could mean low LP pressure due to a weak or faulty regulator.

Furnace runs for a short time, shuts off too soon.

This is typically due to weak house batteries that are sulfated and do not hold a charge very long as mentioned earlier.  Once the furnace shuts off, immediately check voltage at the control board, anything below 11-volts will create this situation.  Even if the rig is plugged into shoreline power, the converter or battery charger will not engage until the batteries hit 10.5-volts so there may be a power gap between what the furnace needs to light and the converter senses for charging.

It can also mean the high limit switch is getting too hot due to obstruction in the vents or is getting weak.

Give your furnace a helping hand!
It’s important to understand your furnace systems’ capacity and sometimes provide a little help with supplemental heat and additional insulation.  A catalytic heater is a safe supplement in the bedroom at night or living area in the daytime.

Mr. Buddy Heater

Check out the articles in our archive on Tips for winter camping and learn about skirting the underside of your rig, insulating the windows, and finding leaks that would allow warm air to escape.


Dave Solberg: Managing Editor, RV Repair Club

For the last 25 years, Dave has conducted RV maintenance and safety seminars, developed dealer and owner training programs, written RV safety and handyman articles, authored an RV handbook reference guide and logged over 100,000 miles on the road in an RV.

RV Repair ClubRV Repair Club is your go-to online resource for enthusiasts who want quality RV maintenance, repair and upgrade information – a community where passionate RVers can come together to gather knowledge and share their experiences.

Learn more about RV Repair Club.

Tire Discounts

Aww Shucks!

Deborah B. ~ “We believe that our money on having Coach-Net is WELL spent. Great service!”

Share this with your friends:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on Pinterest (Opens in new window) Pinterest
  • Print (Opens in new window) Print
  • Email a link to a friend (Opens in new window) Email
  • More
  • Share on Reddit (Opens in new window) Reddit
  • Share on Tumblr (Opens in new window) Tumblr

Like this:

Like Loading...

The Heat is On – part 2

12 Tuesday Apr 2016

Posted by Coach-Net in Tech Tips

≈ Leave a comment

Tags

Combustion Chamber, Propane System, RV Furnace, RV Furnace Voltage, RV Safety, RV tech tip, Sail Switch, Short-Cycling, tech tip

Furnace P2 header Last week I published an overview article on how direct spark ignition forced-air RV furnaces work. This week I will discuss some possible failure modes and troubleshooting steps to help keep the appliance functioning properly.

Unlike other RV appliances, furnaces utilize a purge cycle and are also prone to short-cycling. These characteristics are relevant because they may cause the user to believe the furnace is not working properly. During the purge cycle, the furnace blower will run for up to thirty seconds before the burner lights and after the burner shuts off when the requested temperature is met. This is to ensure that the combustion chamber has adequate air available and does not have any residual gas present. At the end of the heating cycle, the purge acts to cool the combustion chamber. This may leave some owners feeling that their furnaces are malfunctioning, since the appliance will blow cold air for a short time. You should hear your furnace burner ignite after the blower starts, but there could be a delay of up to thirty seconds. Also note that there may be a slight delay between turning on the furnace or setting the temperature and the blower motor starting.

snow covered RVWith short-cycling, the furnace will shut down before the set temperature is reached. This is a common problem in very cold weather and results from the furnace overheating before the RV heats up. This is a normal occurrence meant to protect the furnace and does not indicate a faulty appliance. When this occurs, the furnace will relight when it cools down. Short-cycling may occur more than once in a heating cycle, but eventually the RV will reach the set temperature and the short-cycling will stop. If your furnace short-cycles, be patient, as it may take slightly longer for the RV to heat up. You may choose to slightly reduce the set temperature.

The most common failure mode of an RV furnace is low voltage. Because it uses a blower motor, the furnace is the RV appliance most susceptible to low-voltage failure. A furnace will not run if the house battery voltage falls below 10.5 volts. Voltages higher than 10.5, but lower than the nominal 12V may allow the blower to start but prevent the burner from lighting. This is because the sail switch will fail to close under low airflow conditions. This switch is designed to close and allow current to flow to the ignitor when adequate airflow is achieved. Since low voltage will prevent the blower from spinning fast enough, the sail switch will not close and the furnace will not light.

If your furnace will not start or if the burner does not light after thirty seconds, measure the battery voltage, as well as the voltage reaching the furnace. This can be measured at the fuse panel or at the red and white or black and white wires at the furnace control board. If the voltage is lower than about 11V, you should identify and rectify the cause of the low voltage then test the furnace for proper operation.

Propane If the furnace blower starts and the burner tries to light but fails, I would first check the propane system. Make sure your other propane appliances are functioning properly. It is a good idea to have your propane system inspected annually by a qualified RV service center.

If your furnace is not functioning properly, your battery voltage is higher than 11V, and your propane system is functioning properly, you should have your RV furnace professionally repaired. The problem could lie with the control board, limit switch, sail switch, gas valve, blower, wiring, or elsewhere.  Fortunately, most furnace problems are voltage-related.

About the Author: 

Steve Froese, an avid RV owner, traveler, and Coach-Net member since 2013, is the principal of “A Word to the Wise Technical Communications”, a published RV author, certified RV technician, and licensed Professional Engineer. He frequently collaborates with the “RV Doctor”, Gary Bunzer, and has worked with the RVIA/RVDA as a technical and training writer and consultant. Professionally, he works as a quality engineer and musician. Watch for more of Steve’s work in upcoming Coach-Net publications.

RV Protect

Share this with your friends:

  • Share on Facebook (Opens in new window) Facebook
  • Share on X (Opens in new window) X
  • Share on Pinterest (Opens in new window) Pinterest
  • Print (Opens in new window) Print
  • Email a link to a friend (Opens in new window) Email
  • More
  • Share on Reddit (Opens in new window) Reddit
  • Share on Tumblr (Opens in new window) Tumblr

Like this:

Like Loading...

Subscribe

To subscribe to our monthly enewsletter, visit the homepage www.Coach-Net.com

Coach-Net Members

Access your benefits and services by logging in to My Coach-Net

Categories

  • Favorite Recipes
  • Getting To Know You
  • Healthy Lifestyle
  • Holidays in your RV
  • Kids and Camping
  • National Parks
  • Roadside Assistance
  • RV Information
  • RV Newbie
  • RV Safety
  • Tailgating
  • Tech Tips
  • The Great Outdoors
  • Tips & Tricks
  • Travel Destinations
  • Traveling with your Pet
  • Uncategorized
  • We Love It. We Live It.

Archives

Follow Us

  • Facebook
  • X
  • Instagram
© Coach-Net. All Right Reserved. Unauthorized use and/or duplication of this material without express and written permission from this blog’s author and/or owner is strictly prohibited. Excerpts and links may be used, provided that full and clear credit is given to Coach-Net and with appropriate and specific direction to the original content.

Powered by WordPress.com.

 

Loading Comments...
 

    %d